| Date |
Text |
| 2020-09-21 15:53:46 | 09/21/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. PLEASE PROVIDE A SHOWER DETAIL, OR PLACE A NOTE: |
| | SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS |
| | PRE-PITCHED BENEATH BEFORE LINER INSTALLATION OF 1/4" |
| | IN PER FOOT TOWARD THE DRAIN, MUST HAVE A DAM CORNER, |
| | BACKING AROUND THE PERIMETER AND BEFORE THE FINAL |
| | MORTAR APPLICATION PLACE SOME PEA GRAVEL OVER WEEP |
| | HOLES SO THE MORTAR DOES NOT COVER THEM PER |
| | MANUFACTURES SPECIFICATIONS. |
| | |
| | 3. A STEAM IS SHOWN UP IN THE AIR ON ISOMETRIC BUT ON |
| | THE ELECTRIC PAGE, IT SAYS IT'S UNDER THE SEAT, PLEASE |
| | CLARIFY ON ISOMETRIC AND PLEASE PROVIDE MANUFACTURE |
| | SPECIFICATION. IF THE STEAM UNIT IS UNDER A SHOWER |
| | SEAT, HOW IS THE STEAM ENTERING THE SHOWER? PLEASE |
| | CLARIFY WHAT TYPE OF PROTECTION IS BEING USED AND SHOW |
| | WHERE IT GOING IN THE SHOWER. WPB AMENDMENTS TO THE FBC |
| | 107.2.1A-2. |
| | |
| | 4. PLEASE SHOW HOW OR NOTE HOW THE DRAIN FOR THE STEAM |
| | UNIT IS GOING TO BE PROTECTED FROM RODENT INFILTRATION |
| | PER THE 2017 FBC SEC. R 2606.1. |
| | |
| | 5. THE WATER HEATER IS OUTSIDE AND REQUIRES HOT WATER |
| | PIPES THAT ARE NOT IN A CONDITIONED SPACE TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| | 403.5.3. |
| | |
| | 6. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF |
| | THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE |
| | REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBODIMENT DEPTH |
| | INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS, AND THE SPACING OF THE DOWELS ON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR A FINAL INSPECTION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |