Plan Review Notes
Plan Review Notes For Permit 20070724
Permit Number 20070724
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-21 15:53:4609/21/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE A SHOWER DETAIL, OR PLACE A NOTE:
 SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH BEFORE LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE A DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE THE FINAL
 MORTAR APPLICATION PLACE SOME PEA GRAVEL OVER WEEP
 HOLES SO THE MORTAR DOES NOT COVER THEM PER
 MANUFACTURES SPECIFICATIONS.
  
 3. A STEAM IS SHOWN UP IN THE AIR ON ISOMETRIC BUT ON
 THE ELECTRIC PAGE, IT SAYS IT'S UNDER THE SEAT, PLEASE
 CLARIFY ON ISOMETRIC AND PLEASE PROVIDE MANUFACTURE
 SPECIFICATION. IF THE STEAM UNIT IS UNDER A SHOWER
 SEAT, HOW IS THE STEAM ENTERING THE SHOWER? PLEASE
 CLARIFY WHAT TYPE OF PROTECTION IS BEING USED AND SHOW
 WHERE IT GOING IN THE SHOWER. WPB AMENDMENTS TO THE FBC
 107.2.1A-2.
  
 4. PLEASE SHOW HOW OR NOTE HOW THE DRAIN FOR THE STEAM
 UNIT IS GOING TO BE PROTECTED FROM RODENT INFILTRATION
 PER THE 2017 FBC SEC. R 2606.1.
  
 5. THE WATER HEATER IS OUTSIDE AND REQUIRES HOT WATER
 PIPES THAT ARE NOT IN A CONDITIONED SPACE TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE
 403.5.3.
  
 6. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF
 THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE
 REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBODIMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS, AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved