Plan Review Notes
Plan Review Notes For Permit 20070724
Permit Number 20070724
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-21 16:33:5909/21/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING TIKI TORCH. PLEASE PROVIDE ALL MANUFACTURES
 SPECIFICATION FOR TIKI, GRILL (ONLY BTU'S), NEW RANGE,
 NEW CLOTHING DRYER, POOL HEATER (ONLY BTU'S), AND NEW
 OUTSIDE HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH 2017
 FBC RES. SEC. G2408.1.
  
 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION BUT IT SHALL
 BE SUBMITTED FOR REVIEW AND COMPLIANCE PER THE 2017 FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 5. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 6. PLEASE LABEL DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT
 FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017
 FBC RES. SEC. G2419.2.
  
 7. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE EXISTING SYSTEM IN LEGEND TYPE MATER
 WITH TOTAL. REFER TO THE 2017 FBC RES. SEC. G2413.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR (CLOTHES
 DRYERS AND RANGE) PER THE 2017 FBC RES. SEC. G2407.1
 AND G2439.4.
  
 9. IF USING METAL LOUVERS, SHOW THE LOCATION OF THE
 METAL LOUVERS THAT ARE BEING INSTALLED FOR THE
 COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 10. IF GAS UNITS REQUIRE CONDENSATE AND IT NEEDS TO BE
 1' AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5.
  
 11. PLEASE SHOW ON HOUSE PLANS THE LOCATION OF THE
 TANK-LESS WATER HEATER AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  