| 2020-09-21 16:33:59 | 09/21/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING TIKI TORCH. PLEASE PROVIDE ALL MANUFACTURES |
| | SPECIFICATION FOR TIKI, GRILL (ONLY BTU'S), NEW RANGE, |
| | NEW CLOTHING DRYER, POOL HEATER (ONLY BTU'S), AND NEW |
| | OUTSIDE HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 |
| | FBC RES. SEC. G2408.1. |
| | |
| | 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION BUT IT SHALL |
| | BE SUBMITTED FOR REVIEW AND COMPLIANCE PER THE 2017 FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | |
| | 5. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 6. PLEASE LABEL DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT |
| | FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017 |
| | FBC RES. SEC. G2419.2. |
| | |
| | 7. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE EXISTING SYSTEM IN LEGEND TYPE MATER |
| | WITH TOTAL. REFER TO THE 2017 FBC RES. SEC. G2413. |
| | |
| | 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR (CLOTHES |
| | DRYERS AND RANGE) PER THE 2017 FBC RES. SEC. G2407.1 |
| | AND G2439.4. |
| | |
| | 9. IF USING METAL LOUVERS, SHOW THE LOCATION OF THE |
| | METAL LOUVERS THAT ARE BEING INSTALLED FOR THE |
| | COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN |
| | EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF |
| | THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO |
| | FBC SEC.107.2.1. |
| | |
| | 10. IF GAS UNITS REQUIRE CONDENSATE AND IT NEEDS TO BE |
| | 1' AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5. |
| | |
| | 11. PLEASE SHOW ON HOUSE PLANS THE LOCATION OF THE |
| | TANK-LESS WATER HEATER AND DISTANCE OF ANY OPERABLE |
| | DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE |
| | LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |