Plan Review Notes
Plan Review Notes For Permit 20070724
Permit Number 20070724
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-23 08:56:34ALTERATION LEVEL III
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING S2.0 SHOWS "EXISTING ROOFING SYSTEM TO
 REMAIN - YET YOU HAVE ROOFING SYSTEMS UPLOADED TO
 PROJECTDOX.
 2) PLEASE PROVIDE DETAILS OR A STATEMENT ON THE DRAWING
 ON HOW AND TO WHAT EXTENT YOU WILL BE USING TO COMPLY
 WITH FBC EXISTING BUILDING 706.8
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLEFAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 3) PLEASE SHOW THE ROOF WIND DESIGN PRESSURES ON THE
 DRAWING. (ZONES ARE SHOWN BUT THE PRESSURES ARE NOT).
 4) PLEASE SHOW THE ROOF SLOPES.
 5) MIAMI DADE NOA 19-0311.04 IS A ROOFING SYSTEM - NOT
 AN UNDERLAYMENT - IS THERE A FLAT ROOF TO BE REROOFED?