Plan Review Notes
Plan Review Notes For Permit 20070718
Permit Number 20070718
Review Stop E
Sequence Number 2
Notes
Date Text
2020-08-26 10:30:34PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
 PROVIDE DOCUMENTATION THAT THE PROPOSED 22KW GENERATOR
 IS CAPABLE OF SUPPLYING THE DEMAN LOADS OF THE
 RESIDENCE.
  
 NOTE: LOAD CALC'S RECOMMEND A 30 KW GENERATOR. PROPOSED
 GENERATOR IS ONLY 22KW. IS THIS GENERATOR UNDERSIZED?
 IS OWNER AWARE OF THESE CALCULATIONS AND GENERATOR SIZE
 RECOMMENDATION?
  
 1) RISER
  
 1A) INCLUDE EXISTING SERVICE. INDICATE IF THE SERVICE
 AND MDC ARE EXISTING OR NEW.
 1B) INCLUDE GROUNDING ELECTRODE SYSTEM. IF EXISTING
 SERVICE THIS IS NOT REQUIRED ON RISER DIAGRAHM.
 1C) INCLUDE INTERSYSTEM BONDING CONNECTION. IF EXISTING
 SERVICE THIS IS NOT REQUIRED ON RISER DIAGRAHM.
  
 2) PROVIDE SPECIFICATIONS FOR COMPOSITE CABLE. IF
 COMPOSITE CABLE WILL BE ENCASED IN CONDUIT, PROVIDE
 SIZE AND TYPE OF CONDUIT.
  
 3) PROVIDE SPECIFICATIONS FOR GENERATOR CONTROLLERS.
  
  