| 2020-08-26 10:30:34 | PLAN REVIEW GENERATOR - ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. |
| | PROVIDE DOCUMENTATION THAT THE PROPOSED 22KW GENERATOR |
| | IS CAPABLE OF SUPPLYING THE DEMAN LOADS OF THE |
| | RESIDENCE. |
| | |
| | NOTE: LOAD CALC'S RECOMMEND A 30 KW GENERATOR. PROPOSED |
| | GENERATOR IS ONLY 22KW. IS THIS GENERATOR UNDERSIZED? |
| | IS OWNER AWARE OF THESE CALCULATIONS AND GENERATOR SIZE |
| | RECOMMENDATION? |
| | |
| | 1) RISER |
| | |
| | 1A) INCLUDE EXISTING SERVICE. INDICATE IF THE SERVICE |
| | AND MDC ARE EXISTING OR NEW. |
| | 1B) INCLUDE GROUNDING ELECTRODE SYSTEM. IF EXISTING |
| | SERVICE THIS IS NOT REQUIRED ON RISER DIAGRAHM. |
| | 1C) INCLUDE INTERSYSTEM BONDING CONNECTION. IF EXISTING |
| | SERVICE THIS IS NOT REQUIRED ON RISER DIAGRAHM. |
| | |
| | 2) PROVIDE SPECIFICATIONS FOR COMPOSITE CABLE. IF |
| | COMPOSITE CABLE WILL BE ENCASED IN CONDUIT, PROVIDE |
| | SIZE AND TYPE OF CONDUIT. |
| | |
| | 3) PROVIDE SPECIFICATIONS FOR GENERATOR CONTROLLERS. |
| | |
| | |