2020-07-31 13:52:53PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: LOAD CALC'S RECOMMEND A 30 KW GENERATOR. PROPOSED
 GENERATOR IS ONLY 22KW. IS THIS GENERATOR UNDERSIZED?
 IS OWNER AWARE OF THESE CALCULATIONS AND GENERATOR SIZE
 RECOMMENDATION?
  
 1) RISER
  
 1A) INCLUDE EXISTING SERVICE.
 1B) INCLUDE GROUNDING ELECTRODE SYSTEM.
 1C) INCLUDE INTERSYSTEM BONDING CONNECTION.
  
 2) PROVIDE SPECIFICATIONS FOR COMPOSITE CABLE. IF
 COMPOSITE CABLE WILL BE ENCASED IN CONDUIT, PROVIDE
 SIZE AND TYPE OF CONDUIT.
  
 3) PROVIDE SPECIFICATIONS FOR GENERATOR CONTROLLERS.
  
  
  
  
  
  
  
  
  
  
  
  