| Plan Review Notes For Permit 20070718 |
| Permit Number |
20070718 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-31 13:52:53 | PLAN REVIEW GENERATOR - ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTE: LOAD CALC'S RECOMMEND A 30 KW GENERATOR. PROPOSED | | | GENERATOR IS ONLY 22KW. IS THIS GENERATOR UNDERSIZED? | | | IS OWNER AWARE OF THESE CALCULATIONS AND GENERATOR SIZE | | | RECOMMENDATION? | | | | | | 1) RISER | | | | | | 1A) INCLUDE EXISTING SERVICE. | | | 1B) INCLUDE GROUNDING ELECTRODE SYSTEM. | | | 1C) INCLUDE INTERSYSTEM BONDING CONNECTION. | | | | | | 2) PROVIDE SPECIFICATIONS FOR COMPOSITE CABLE. IF | | | COMPOSITE CABLE WILL BE ENCASED IN CONDUIT, PROVIDE | | | SIZE AND TYPE OF CONDUIT. | | | | | | 3) PROVIDE SPECIFICATIONS FOR GENERATOR CONTROLLERS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|