| Notes |
| Date |
Text |
| 2020-07-24 10:51:33 | SHUTTERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ON THE " SCHEDULE FOR INSTALLATION OF OPENING | | | PROTECTIVE DEVICES OR ASSEMBLIES" IN THE COLUMN LABELED | | | " SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT | | | APPROVAL" PLEASE SHOW THE LETTER OF THE MOUNTING TYPE | | | FOR TOP AND BOTTOM - SEE PRODUCT APPROVAL MOUNTING | | | TYPES TOP/BOTTOM - A,B,C,D, ETC. (A/B - D/E ETC.) | | | |
|