| 2020-07-22 07:34:24 | 1.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, ( MP |
| | REGULATOR ) TO THE GENERATOR.PER THE 2017 FBC-FUEL GAS |
| | SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, |
| | G2413.4.2. |
| | 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. FGC SECS. 401.4, |
| | 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4, |
| | G2412.8, G2413.1, G2413.2, G2413.3. |
| | 3) INDICATE ON THE GAS DRAWING HOW THE EXISTING SYSTEM |
| | WILL BE RETROFITTED TO HANDLE THE 2 PSI SYSTEM. |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC |
| | SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| | 5) THE GALVANIZED PIPING SHALL BE LOCATE A MINIMUM OF 3 |
| | 1/2/ INCHES ABOVE GRADE. FBC-FUEL GAS SEC. 404.9. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |