| Plan Review Notes For Permit 20070654 |
| Permit Number |
20070654 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-06 10:22:35 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD INFORMATION SUBMITTED DOES NOT | | | MEET THE REQUIREMENTS FOR PREFABRICATED SLABS. | | | PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE | | | PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING FROM A | | | FLORIDA LICENSED ENGINEER. FBC 107.3.4 |
|