| 2020-08-04 16:26:25 | 08/04/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING TANKLESS WATER HEATER. A FULL EVALUATION OF |
| | ALL GAS EQUIPMENT WILL BE DONE AT FIELD, IF NOT TO |
| | CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT |
| | OWNER EXPENSE. |
| | |
| | 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | |
| | 6. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR |
| | 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 7. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER |
| | THE 2017 FBC RES. SEC. G2419.2. |
| | |
| | 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS |
| | ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC |
| | RES. SEC. G2401.1.3. |
| | |
| | 9. ON ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH |
| | OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 10. PLEASE SHOW IF THERE IS A REGULATOR, DRIP LEG, |
| | UNION AND SHUTOFF VALVE ON TANKLESS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 11. PLEASE PROVIDE THE TOTAL BTU'S FOR THE SYSTEM ON |
| | ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 12. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| | (TANKLESS) TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. |
| | G2408.1. |
| | |
| | 13. IF APPLICABLE, PLEASE SHOW HOUSE THE LOCATION OF |
| | THE TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE |
| | OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE |
| | WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL |
| | COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |