| Plan Review Notes For Permit 20070557 |
| Permit Number |
20070557 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-12 18:03:43 | PLAN REVIEW GENERATOR - ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER | | | SWITCH. ATS | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2) ELECTRICAL RISER | | | PROVIDE THE TYPE AND SIZE OF THE GENERATOR CONTROL | | | CIRCUIT CONDUCTORS. NEC 215.5; WPB FBC 107.2.1 | | | |
|