| Plan Review Notes For Permit 20070485 |
| Permit Number |
20070485 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-15 14:24:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLANS DO NOT INDICATE WHAT THE | | | REVISIONS ARE AND WHERE THEY ARE LOCATED. | | | | | | PER NFPA 1 | | | | | | 1.14 PLAN REVIEW. | | | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE | | | REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS, | | | ARE LOCATED. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|