2020-10-14 16:21:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20070477 1540 PALM BEACH LAKES BLVD #120
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1.SECOND REQUEST: A1.0 REFERENCES A5.4/DETAIL 5 FOR
 WATER HEATER PLATFORM. THE DETAIL IS NOT THERE. PER WPB
 FBC 107.1, PROVIDE DETAIL INCLUDING THE ANCHORING FOR
 THE PLATFORM. REGARDING THE SPECIFIED WATER HEATER, IT
 IS 55 INCHES TALL AND FILLED WEIGHS APPROXIMATELY 635
 POUNDS. IT IS BEING MOUNTED ABOVE THE WORKSPACE OF THE
 MOP SINK. INSURE WHEN DESIGNING THE SUPPORT STRUCTURE
 THAT THE UNIT IS SUPPORTED AND RESTRAINED IN A MANNER
 THAT SAFEGUARDS ANYBODY WORKING BELOW. (SEE ORIGINAL
 COMMENT #4)
 ENGINEER RESPONSE: ARCHITECT TO RESPOND; ARCHITECT DID
 NOT RESPOND AND A1.0 NO LONGER MAKES ANY REFERENCE TO
 THE WATER HEATER PLATFORM. TO BE CLEAR, A DETAIL AS
 OUTLINED IN THE ORIGINAL COMMENT IS STILL REQUIRED,
 EITHER BY THE ARCHITECT OR THE ENGINEER.
  
 2. SECOND REQUEST: A1.0 REFERENCES A5.4/DETAIL 5 FOR
 WATER HEATER PLATFORM. THE DETAIL IS NOT THERE. PER WPB
 FBC 107.1, PROVIDE DETAIL INCLUDING THE ANCHORING FOR
 THE PLATFORM. REGARDING THE SPECIFIED WATER HEATER, IT
 IS 55 INCHES TALL AND FILLED WEIGHS APPROXIMATELY 635
 POUNDS. IT IS BEING MOUNTED ABOVE THE WORKSPACE OF THE
 MOP SINK. INSURE WHEN DESIGNING THE SUPPORT STRUCTURE
 THAT THE UNIT IS SUPPORTED AND RESTRAINED IN A MANNER
 THAT SAFEGUARDS ANYBODY WORKING BELOW. (SEE ORIGINAL
 COMMENT #4)
 ENGINEER RESPONSE: ARCHITECT TO RESPOND; ARCHITECT DID
 NOT RESPOND AND A1.0 NO LONGER MAKES ANY REFERENCE TO
 THE WATER HEATER PLATFORM. TO BE CLEAR, A DETAIL AS
 OUTLINED IN THE ORIGINAL COMMENT IS STILL REQUIRED,
 EITHER BY THE ARCHITECT OR THE ENGINEER.
  
 3.NEW COMMENT: REVISED DRAWINGS SHOW THE BACKFLOW
 PREVENTER ON THE CITY SIDE OF THE METER. CITY OF WEST
 PALM BEACH UTILITIES STANDARD DETAIL WS-11 FROM MANUAL
 FOR CROSS CONNECTION CONTROL REQUIRES BACKFLOW
 PREVENTER TO BE DOWNSTREAM OF THE METER. PER WPB FBC
 107.2.1, CLARIFY OR CORRECT.
  
 4.NEW COMMENT: ZURN Z1021 TRAP PRIMER CALLED OUT ON
 P0.2 PLUMBING FIXTURE SCHEDULE IS DESIGNED TO BE
 CONNECTED TO THE LAVATORY WASTE. IT IS SHOWN ON NEW
 DRAWING P2.1 WATER RISER BEING CONNECTED TO THE WATER
 SUPPLY AT THE WATER CLOSET. P1.1 ALSO SHOWS THE SAME
 AND NOTE 9 CALLS FOR TRAP PRIMER TO BE INSTALLED HIGH
 IN THE CEILING WITH AN ACCESS PANEL. ADDITIONALLY,
 P0.2, DETAIL 5; TYPICAL FLOOR DRAIN DETAIL LISTS A
 Z1072 TRAP GUARD AND A Z1022 WATER SUPPLIED TRAP
 PRIMER. PER WPB FBC 107.2.1, CLARIFY. IF WATER SUPPLIED
 THEN PROVIDE A SPECIFICATION AND DETAIL; IF NOT THEN
 PROVIDE NOTE IN PLUMBING FIXTURE SCHEDULE, CHANGE NOTE
 9 TO REFLECT AND ELIMINATE ALL REFERENCES TO WATER
 SUPPLIED CONNECTIONS. ADDITIONALLY, NO EXCEPTION IS
 TAKEN TO THE Z1072 TRAP GUARD. JUST BE CLEAR.
  
 5.NEW COMMENT: OCCUPANCY IS A-2 RESTAURANT WITH
 OCCUPANT LOAD OF FIFTEEN (15) PERSONS. UNFORTUNATELY
 FOOTNOTE E ALLOWING EXCEPTION FOR REQUIRED SERVICE SINK
 IS NOT APPLICABLE. IT IS ONLY ALLOWED FOR BUSINESS B
 AND MERCANTILE M. PROVIDE SERVICE SINK AS REQUIRED BY
 FBC PL TABLE 403.1.
  
 6.NEW COMMENT: CONDENSATE FROM COOLER EVAPORATOR SHALL
 NOT DISCHARGE TO THE GREASY WASTE PER FBC PL 1003.2.
 ADDITIONALLY, PER WPB CODE OF ORDINANCE CHAPTER 90,
 ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE (I INTERPRET
 THIS AS ANY CONDENSATION FROM EVAPORATOR COILS) SHALL
 NOT DISCHARGE TO THE CITY UTILITIES SANITARY SEWAGE
 INFRASTRUCTURE WITHOUT PERMISSION FROM THE UTILITIES
 DEPARTMENT. YOU MAY CONTACT MR. MANNY GONZALES IN
 ENGINEERING AT 561-494-1128 FOR ADDITIONAL INFORMATION.
 MOVING FORWARD, DISCHARGE THE CONDENSATE TO AN EXTERIOR
 DRYWELL; PROVIDE DETAIL.
  
 6.NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DESCRIPTION
 AND MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL
 FOR WF-1; IF THIS IS A WATER FILTER THEN A BACKFLOW
 PREVENTER IS REQUIRED.
  
 7. NEW COMMENT: PER FBC PL 606.1(1) AND (5) PROVIDE
 FULL OPEN VALVES ON THE WATER DISTRIBUTION SUPPLY PIPE
 AT THE ENTRANCE INTO THE STRUCTURE AND AT THE TOP OF
 EVERY DOWN FEED PIPE. TO PREVENT INTERRUPTION IN THE
 HOT WATER RECIRCULATING SYSTEM, DO NOT INCLUDE HOT
 WATER DROP IN THE LOOP.
  
 8. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE
 DESCRIPTION AND MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR MV-1
 (THERMOSTATIC MIXING VALVE?); PER FBC PL 416.5,
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070
 IT IS NOTED THAT THE HOT WATER SYSTEM IS 140 DEGREES
 FAHRENHEIT. THIS TEMPERATURE IS SCALDING AND IS BEING
 DELIVERED TO THE TWO (2) HAND SINKS (ITEM 12). THERE IS
 NO PROVISION AT THE SINKS TO REDUCE THE TEMPERATURE AT
 THE POINT OF USE. PER WPB FBC 107.2.1, CLARIFY
  
 9.NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAILS FOR
 INDIRECT WASTES FROM SINGLE COMPARTMENT (ITEM 13) AND
 THREE COMPARTMENT (ITEM 17) SCULLERY SINKS.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  