| 2020-10-14 13:23:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20070477 1540 PALM BEACH LAKES BLVD #120 |
| | |
| | 2ND REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1.SECOND REQUEST-RE: P1.1, NOTE 13, EMERGENCY HOOD SHUT |
| | DOWN SHUT OFF VALVE AND ASSEMBLY SHALL BE BELOW THE |
| | CEILING, NOT ABOVE. SEE NFPA 96-08 SECS. 10.4, 10.5. |
| | (SEE ORIGINAL COMMENT #1) |
| | |
| | 2.SECOND REQUEST; SHOW SIZE AT INDIVIDUAL SUPPLY TO |
| | EQUIPMENT. (SEE ORIGINAL COMMENT #2) |
| | |
| | 3.NEW COMMENT: AS THE SYSTEM PRESSURE IS CONFIRMED TO |
| | BE 0.5 PSI (LESS THAN 2 PSI/1PSI DROP), WHY ARE THE 0.5 |
| | REGULATORS STILL SHOWN ON PIPING DRAWINGS AND WATER |
| | HEATER DETAIL? PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| | (SEE ORIGINAL COMMENT #4) |
| | |
| | 4.RE: ENGINEER'S RESPONSE TO ORIGINAL COMMENT #7: |
| | CHANGED TO BE INSTALLED THROUGH THE ROOF. |
| | STILL NEED TO SHOW LOCATION ON THE ROOF AND DISTANCE TO |
| | CLOSEST VENTILATION OPENING AS WELL AS A DETAIL |
| | PROVIDING ANCHORING AND SUPPORT DETAILS. |
| | |
| | 5.ENGINEER'S RESPONSE TO ORIGINAL COMMENT #8: SEE |
| | ATTACHED WATER HEATER CUT SHEET |
| | WATER HEATER CUT SHEET ONLY SHOWS SKETCHES OF |
| | HORIZONTAL AND VERTICAL INSTALLATIONS. AGAIN, PLEASE |
| | PROVIDE MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL FOR CONCENTRIC VENT. IT SHOULD BE NOTED THAT THE |
| | MODEL SP12161 CONCENTRIC VENT REFERENCED IN THE DETAILS |
| | ON THE CUT SHEET AND THE PLANS HAS BEEN DISCONTINUED |
| | SINCE 2014. |
| | |
| | 6.ENGINEER?S RESPONSE TO ORIGINAL COMMENT #10: THE |
| | KITCHEN HOOD IS PROVIDED BY THE KITCHEN EQUIPMENT |
| | SUPPLIER TO MEET THE REQUIREMENTS OF THE PIZZA OVEN. |
| | THE WATER HEATER IS A POWER DIRECT VENT. |
| | NO ISSUE IS TAKEN WITH THE WATER HEATER. HOWEVER, |
| | COMBUSTION AIR IS REQUIRED FOR THE PIZZA OVENS IN |
| | ADDITION TO MAKE UP AIR (TO REPLACE EXHAUSTED AIR) AND |
| | COMBUSTION AIR CALCULATIONS ARE REQUIRED FOR THE PIZZA |
| | OVENS; IT IS THE ENGINEER?S RESPONSIBILITY TO PROVIDE |
| | THOSE CALCULATIONS. COMBUSTION AIR IS REQUIRED IN |
| | ADDITION TO MAKE UP AIR. PLEASE NOTE THAT I HAVE |
| | REVIEWED THE KITCHEN HOOD INFORMATION SHEET PROVIDED |
| | FOR REFERENCE AND THERE IS ONLY MAKE UP AIR PROVIDED ON |
| | THE DRAWING. |
| | |
| | 7.NEW COMMENT: RE: P2.2-REVISED SIZING CHART PROVIDED |
| | FBC FG TABLE 402.4(2) IS FOR SCHEDULE 40 METALLIC PIPE. |
| | PER WPB FBC 107.2.1, REMOVE MATERIAL SPECIFICATION |
| | ALLOWING COPPER TUBING NOTED ON P2.2 AND ON P0.1. |
| | |
| | 8.NEW COMMENT: P2.2 GAS PIPING NOTE 6; ADD TO NOTE THE |
| | WORDS GAS VALVES SHALL CONFORM TO FBC FG TABLE |
| | 409.1.1-MANUAL GAS VALVE STANDARDS |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20070477 1540 PALM BEACH LAKES BLVD #120 |
| | |