2020-08-27 13:57:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20070477 1540 PALM BEACH LAKES BLVD #120
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PER FBC ACC 609.4, REQUIRED HORIZONTAL SIDE WALL AND
 BACK WALL GRAB BARS AT THE WATER CLOSET SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP (NOT THE CENTER) OF THE GRIPPING SURFACE,
  
 2. PER FBC ACC 603.3, MIRRORS LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3. PER WPB FBC 107.2.1, COORDINATE PLAN SHEET G-3 WITH
 PLAN SHEETS A-5.0 AND A-5.1
  
 4. A1.0 REFERENCES A5.4/DETAIL 5 FOR WATER HEATER
 PLATFORM. THE DETAIL IS NOT THERE. PER WPB FBC 107.1,
 PROVIDE DETAIL INCLUDING THE ANCHORING FOR THE
 PLATFORM. REGARDING THE SPECIFIED WATER HEATER, IT IS
 55 INCHES TALL AND FILLED WEIGHS APPROXIMATELY 635
 POUNDS. IT IS BEING MOUNTED ABOVE THE WORKSPACE OF THE
 MOP SINK. INSURE WHEN DESIGNING THE SUPPORT STRUCTURE
 THAT THE UNIT IS SUPPORTED AND RESTRAINED IN A MANNER
 THAT SAFEGUARDS ANYBODY WORKING BELOW.
  
 5. PER WPB FBC 107.2.1 107.3.5.1.3, PROVIDE A WATER
 RISER DIAGRAM. SHOW ALL VALVES, WHA, THERMOSTATIC
 MIXING VALVE AND BACKFLOW DEVICES AND IDENTIFY THE
 FIXTURES/ EQUIPMENT BEING CONNECTED.
  
 6. PER WPB FBC 107.2.1 107.3.5.1.3, PROVIDE A SANITARY
 RISER DIAGRAM; IDENTIFY THE FIXTURES/ EQUIPMENT BEING
 CONNECTED.
  
 7. PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR MANHOLE ACCESS TO GREASE INTERCEPTOR.
 IF IN VEHICULAR TRAFFIC AREA PROVIDE TRAFFIC LOAD
 BEARING STRUCTURE.
  
 8. PER WPB FBC 107.2.1, SHOW THE LOCATION AND TYPE OF
 EXISTING BACKFLOW PREVENTER FOR THE WATER SERVICE. IF
 NONE THEN PROVIDE SPECIFICATION, LOCATION AND DETAIL
 FOR A COMPLIANT BACKFLOW PREVENTER.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH