| 2020-08-27 13:27:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20070477 1540 PALM BEACH LAKES BLVD #120 |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | 1.PER WPB FBC 107.2.1 AND 107.3.5.1.5, SUBMIT AN |
| | ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER FBC FG SECS. 402.4.1, 402.4.2. |
| | CLEARLY SHOW THE LOCATION OF ALL MP (STEP-DOWN) |
| | REGULATORS, VALVES AND UNIONS AS WELL AS THE EMERGENCY |
| | HOOD SHUT DOWN SHUT OFF VALVE BELOW THE CEILING. A |
| | MANUAL SHUTOFF VALVE SHALL BE UPSTREAM AND THE UNION |
| | SHALL BE DOWNSTREAM OF THE MANUAL VALVE PER NFPA 96-08 |
| | SECS. 10.4, 10.5. |
| | |
| | 2.CLEARLY SHOW THE TYPE OF PIPE MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| | NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE. |
| | |
| | 3.RE: P1.1/NOTE 12. PER WPB FBC 107.2.1 INDICATE THE |
| | DELIVERY PRESSURE OF THE NEW GAS METER. |
| | |
| | 4. P0.1 GAS PIPE SIZING REFERENCES FBC FG TABLE |
| | 402.4(5) INDICATING 2PSI/1PSI DROP, BUT DESCRIBES THE |
| | SYSTEM AS LESS THAN 2PSI/ 0.5PSI DROP. PLAN SHEET P1.1 |
| | GAS DISTRIBUTION IDENTIFIES PIPING AT 0.5PSI AND CALLS |
| | FOR A 0.5PSI REGULATOR AT THE OVEN. ADDITIONALLY, THE |
| | WATER HEATER DETAIL ON PLAN SHEET PO.2 SHOWS A |
| | REGULATOR. PER WPB FBC 107.2.1, CLARIFY. PLEASE NOTE |
| | THAT IF DISTRIBUTION AND METER PROVIDE 2PSI, THEN A |
| | SIZING TABLE(S) AND LOAD DEMANDS ARE REQUIRED FOR THE |
| | PIPING DOWNSTREAM OF THE MP REGULATORS. |
| | |
| | 5. A6.0: EQUIPMENT SCHEDULE; ITEM #7, OVEN APPEARS TO |
| | HAVE TWO (2) GAS CONNECTIONS AT 175 MBTU EACH FOR A |
| | TOTAL OF 350 MBTU. PLAN SHEET P1.1 GAS INDICATES ONE |
| | (1) CONNECTION . PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 6. 7. A6.0: EQUIPMENT SCHEDULE; ITEM #7, OVEN APPEARS |
| | TO HAVE TWO (2) GAS CONNECTIONS AT 175 MBTU EACH FOR A |
| | TOTAL OF 350 MBTU. PO.1 GAS LOAD REQUIREMENTS AND THE |
| | FOOD SERVICE PLUMBING SCHEDULE INDICATE 340 MBTU TOTAL. |
| | PER WPB GBC 107.1, CLARIFY. |
| | |
| | 7. P1.1/NOTE 8 AND PO.2/WATER HEATER DETAIL INDICATE |
| | CONCENTRIC VENT. IT APPEARS THAT IT IS TERMINATING |
| | THROUGH A SIDE WALL PER P1.1/NOTE 8. SUBMIT A DETAIL |
| | SHOWING THE TYPE, LOCATION, SIZE, TERMINATION POINT, |
| | HEIGHT ABOVE THE GRADE AND ANCHORING DETAILS OF THE GAS |
| | VENT(S) PER FBC FG SECS. 502 THRU 505. |
| | |
| | 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION AND INSTALLATION MANUAL FOR CONCENTRIC |
| | VENT. |
| | |
| | 9. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54 AND FBC FG SEC. |
| | 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION PER FBC FG 305.1. |
| | |
| | 10. PER WPB FBC 107.2.1, SUBMIT COMBUSTION AIR |
| | CALCULATIONS FOR THE GAS APPLIANCES. WHERE COMBUSTION |
| | AIR IS PROVIDED BY THE BUILDING'S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR TO COMPLY WITH FBC FG 304.9.3. |
| | |
| | 11. PLAN SHEETS P0.2/DETAIL 4 AND M0.2/DETAIL 5 |
| | INDICATE GAS SUPPLIED TO THE RTU(S). THE PIPING PLAN |
| | AND THE SCHEDULE DOES NOT INDICATE THIS. PER WPB FBC |
| | 107.2.1, CLARIFY. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS COMMENTS FROM THE |
| | FIRST REVIEW. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |