Plan Review Notes
Plan Review Notes For Permit 20070477
Permit Number 20070477
Review Stop G
Sequence Number 1
Notes
Date Text
2020-08-27 13:27:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20070477 1540 PALM BEACH LAKES BLVD #120
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
 1.PER WPB FBC 107.2.1 AND 107.3.5.1.5, SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER FBC FG SECS. 402.4.1, 402.4.2.
 CLEARLY SHOW THE LOCATION OF ALL MP (STEP-DOWN)
 REGULATORS, VALVES AND UNIONS AS WELL AS THE EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE BELOW THE CEILING. A
 MANUAL SHUTOFF VALVE SHALL BE UPSTREAM AND THE UNION
 SHALL BE DOWNSTREAM OF THE MANUAL VALVE PER NFPA 96-08
 SECS. 10.4, 10.5.
  
 2.CLEARLY SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE.
  
 3.RE: P1.1/NOTE 12. PER WPB FBC 107.2.1 INDICATE THE
 DELIVERY PRESSURE OF THE NEW GAS METER.
  
 4. P0.1 GAS PIPE SIZING REFERENCES FBC FG TABLE
 402.4(5) INDICATING 2PSI/1PSI DROP, BUT DESCRIBES THE
 SYSTEM AS LESS THAN 2PSI/ 0.5PSI DROP. PLAN SHEET P1.1
 GAS DISTRIBUTION IDENTIFIES PIPING AT 0.5PSI AND CALLS
 FOR A 0.5PSI REGULATOR AT THE OVEN. ADDITIONALLY, THE
 WATER HEATER DETAIL ON PLAN SHEET PO.2 SHOWS A
 REGULATOR. PER WPB FBC 107.2.1, CLARIFY. PLEASE NOTE
 THAT IF DISTRIBUTION AND METER PROVIDE 2PSI, THEN A
 SIZING TABLE(S) AND LOAD DEMANDS ARE REQUIRED FOR THE
 PIPING DOWNSTREAM OF THE MP REGULATORS.
  
 5. A6.0: EQUIPMENT SCHEDULE; ITEM #7, OVEN APPEARS TO
 HAVE TWO (2) GAS CONNECTIONS AT 175 MBTU EACH FOR A
 TOTAL OF 350 MBTU. PLAN SHEET P1.1 GAS INDICATES ONE
 (1) CONNECTION . PER WPB FBC 107.2.1, CLARIFY.
  
 6. 7. A6.0: EQUIPMENT SCHEDULE; ITEM #7, OVEN APPEARS
 TO HAVE TWO (2) GAS CONNECTIONS AT 175 MBTU EACH FOR A
 TOTAL OF 350 MBTU. PO.1 GAS LOAD REQUIREMENTS AND THE
 FOOD SERVICE PLUMBING SCHEDULE INDICATE 340 MBTU TOTAL.
 PER WPB GBC 107.1, CLARIFY.
  
 7. P1.1/NOTE 8 AND PO.2/WATER HEATER DETAIL INDICATE
 CONCENTRIC VENT. IT APPEARS THAT IT IS TERMINATING
 THROUGH A SIDE WALL PER P1.1/NOTE 8. SUBMIT A DETAIL
 SHOWING THE TYPE, LOCATION, SIZE, TERMINATION POINT,
 HEIGHT ABOVE THE GRADE AND ANCHORING DETAILS OF THE GAS
 VENT(S) PER FBC FG SECS. 502 THRU 505.
  
 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION AND INSTALLATION MANUAL FOR CONCENTRIC
 VENT.
  
 9. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54 AND FBC FG SEC.
 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER FBC FG 305.1.
  
 10. PER WPB FBC 107.2.1, SUBMIT COMBUSTION AIR
 CALCULATIONS FOR THE GAS APPLIANCES. WHERE COMBUSTION
 AIR IS PROVIDED BY THE BUILDING'S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR TO COMPLY WITH FBC FG 304.9.3.
  
 11. PLAN SHEETS P0.2/DETAIL 4 AND M0.2/DETAIL 5
 INDICATE GAS SUPPLIED TO THE RTU(S). THE PIPING PLAN
 AND THE SCHEDULE DOES NOT INDICATE THIS. PER WPB FBC
 107.2.1, CLARIFY.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS COMMENTS FROM THE
 FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20070477 1540 PALM BEACH LAKES BLVD #120