| Plan Review Notes For Permit 20070475 |
| Permit Number |
20070475 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-01 10:51:56 | PLAN REVIEW GENERATOR - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1) STRUCTURAL DETAIL OF THE PRE-CAST GENERATOR PAD | | | SHALL HAVE A VALID DIGITAL SIGNATURE OF THE DESIGN | | | PROFESSIONAL PER FS 471 & FAC 61G15. | | | | | | 2) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR WITH A | | | VALID DIGITAL SIGNATURE OF THE DESIGNER AS REQUIRED FOR | | | THE GENERATOR PAD ENGINEERING PER FBC 107.3.5.3 AND | | | R301.2. | | | | | | 3) ELECTRICAL APPLICATION INDICATES A 500 GAL. U/G TANK | | | SHALL BE INSTALLED. GAS RISER AND GAS SUB-PERMIT | | | INDICATE N/G TO BE INSTALLED. | | | PLEASE CLARIFY. | | | | | | 4) IF U/G TANK WILL BE INSTALLED INDICATE LOCATION OF | | | TANK ON SURVEY. | | | |
|