 SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1. COMPLETE THE FORM PROVIDED AT THE FRONT COUNTER
 "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES" FORM OR PROVIDE ALL INFORMATION
 REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET)
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 3. PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE WINDOW
 TO THE EDGE OF THE BUILDING - FOR THE WINDOWS NEXT TO
 THE CORNERS - NEEDED TO DETERMINE WIND ZONE 4 OR 5.
  
 4. JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE TOO LOW. PLEASE REVISE BUILDING PERMIT
 APPLICATION (SHOW THE JOB VALUE TO INCLUDE LABOR AND
 MATERIAL AS IF A CONTRACTOR IS GOING TO INSTALL THE
 SHUTTERS). FBC 109.3
  
 5. PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL (2 PAGES
 HAVE BEEN PROVIDED) - NEED FRONT PAGES OF THE FLORIDA
 PRODUCT APPROVAL AND THE REST OF THE INSTALLATION
 INSTRUCTIONS.
 HTTPS://WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 FORMS CAN BE PROVIDED BY EMAILING [email protected] AND ASKING
 FOR "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES? FORM.
  