| 2020-08-21 13:00:32 | 1) IF COMBUSTION AIR IS BEING PROVIDED BY THE | | | BUILDING'S MECHANICAL VENTILATION SYSTEM,THE SYSTEM | | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | | ADDITION TO THE REQUIRED VENTILATION AIR. FBC-FUEL GAS | | | SEC. 304.9.3. PROVIDE THIS INFORMATION FOR REVIEW. THE | | | PLAN NOTES THAT AHU -5 & AHU-1 IS SUPPLYING COMBUSTION | | | AIR FOR THE DRYERS. IS THIS UNIT DEDICATED TO SUPPLY | | | JUST THE COMBUSTION AIR FOR THE DRYERS? SHOW COMPLIANCE | | | WITH FBC-FUEL GAS SEC. 304.9.2. | | | 2) EACH OF THE APPLIANCES SERVED SHALL BE INTERLOCKED | | | WITH THE MECHANICAL AIR SUPPLY SYSTEM TO PREVENT MAIN | | | BURNER OPERATION OPERATION WHEN THE MECHANICAL AIR | | | SUPPLY SYSTEM IS NOT IN OPERATION. FBC-FUEL GAS | | | SEC.304.9.2. | | | 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE | | | PRESSURE REGULATOR. FBC-FUEL GAS SEC.410.2 (7). A UNION | | | WAS PLACED ON THE UTILITY SIDE OF THE GAS METER WHICH | | | FALLS UNDER THE GAS UTILITY WHICH WAS NOT IN MY REVIEW | | | COMMENT AND NO UNIONS ARE SHOWN AT THE REGULATORS AS | | | PREVIOUSLY REQUESTED. 2ND REQUEST. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|