| Plan Review Notes For Permit 20070444 |
| Permit Number |
20070444 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-31 06:56:59 | 1) SHT. A7.4 - DETAILS #23 & #19 - THE KNEE CLEARANCE | | | SHALL BE 8 INCHES DEEP MINIMUM AT 27 INCHES ABOVE THE | | | FINISH FLOOR OR GROUND PER FBC-ACCESS. SEC.306.3.3 AND | | | FIGURE 306.3. THE PLAN SHOWS 6 INCHES. | | | 2) SHT. A7.4 - DETAILS #10, #14, & #21 - THE MINIMUM | | | HEIGHT OF THE GRAB BAR IS SHOWN AS 2 FEET 8 INCHES. THE | | | MINIMUM HEIGHT IS 33 INCHES ( 2 FEET 9 INCHES) PER | | | FBC-ACCESS. SEC. 609.4. | | | 3) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. FBC-ACCESS. SEC.603.3. | | | 4) SHT. P3.1 - SHOW THE CONTINUATION POINT OF THE 3/4 | | | INCH GAS LINE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) SUBMIT A REVISED WATER AND SANITARY RISER SHOWING | | | THE ADDED TUB IN THE GROOMING ROOM.WPB AMEND. TO FBC | | | SEC. 107.3.5.1.3. | | | 6) THE HOT WATER SUPPLIED TO BATHTUBS SHALL BE LIMITED | | | TO A MAXIMUM TEMPERATURE OF 120 DEGREES BY A WATER | | | -TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 | | | OR CSA B125.3 PER FBC-PLUMBING SEC.424.5. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|