| Plan Review Notes For Permit 20070444 |
| Permit Number |
20070444 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-04 08:49:36 | 1) ACCORDING TO MY CALCULATIONS, THE BTU LOAD FOR THE | | | GAS SYSTEM IS 2,775,000 BTU'S. REVISE THE BTU LOAD ON | | | SHT. P4.7. | | | 2) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE | | | PRESSURE REGULATOR. FBC-FUEL GAS SEC.410.2 (7). | | | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED | | | DRYER.FBC-FUEL GAS SEC.304.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|