2020-08-08 10:37:23PLAN REVIEW - BUILDING ACCESSORY STRUCTURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE DESIGNED
 PER FBC RES CHPT 3 SECTION R301 OR ASCE 7
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 1. PROVIDE A SITE PLAN....
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDARY LINE SURVEY.
  
 2. PROVIDE THE FOLLOWING PLANS
  
 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING/TIE DOWNS
 2B) PROVIDE BUILDING PLANS WITH REQUIRED DIMENSIONS
 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION
 CONNECTION DETAIL
 2D) PROVIDE A WALL PLAN WITH WALL TO FLOOR CONNECTION
 DETAIL
 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL
 CONNECTION DETAIL
 2F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH
 OPENINGS AND DESIGN WIND LOADS IF APPLICABLE.
 2G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS,
 DOORS AND TIE DOWNS. >720 SQ. FT. SEE R301.2.1.2 BELOW
  
 R301.2.1.2 PROTECTION OF OPENINGS.
 STRUTURES THAT ARE NOT DESIGNED FOR HUMAN HABITATION
 AND THAT HAVE A FLOOR AREA OF 720 SQUARE FEET (67 M2)
 OR LESS ARE NOT REQUIRED TO COMPLY WITH THE MANDATORY
 WIND-BORNE DEBRIS IMPACT STANDARD OF THIS CODE
  
 3. PROVIDE PRODUCT APPROVALS FOR WINDOWS DOORS ROOFING
 AND TIE DOWN ANCHORS
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR AND TIE
 DOWN SUBMITTALS.
  
 4. DESINER SHALL PRINT THEIR NAME AND SIGN EACH PLAN.
 SEE DIGITAL SIGNATURE REVIEW COMMENTS
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  