Plan Review Notes
Plan Review Notes For Permit 20070431
Permit Number 20070431
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-30 11:00:40SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES? NEEDS TO BE FILLED OUT CORRECTLY
 AND PRECISELY - "SHUTTER MOUNTING CONNECTION" SHOULD BE
 SHOWN AS (TOP/BOTTOM) (1T/1B) 1T AND 1B ARE "SHUTTER
 MOUNTING CONNECTIONS. "SPECIFIC ANCHOR TYPE" SHOW
 (TOP/BOTTOM) (A/A1) - (A - IS NOT AN ANCHOR TYPE FOR
 BLOCK) (A1 IS FOR BLOCK) . CHECK YOU ANCHOR SPACING
 SHOWN IN THE "ANCHOR SPACING COLUMN" IT DOES NOT MATCH
 WHAT YOU CIRCLED ON THE PRODUCT APPROVAL (THE SPACING
 CIRCLED ON THE PRODUCT APPROVAL IS LESS THAN 8 INCHES).
  