Plan Review Notes
Plan Review Notes For Permit 20070426
Permit Number 20070426
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-15 16:16:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS FROM THE ENGINEER DO NOT
 SPECIFY THE SYSTEM TYPE OR THE PAGE NUMBER FROM THE NOA
 TO INDICATE WHICH TESTED ASSEMBLY HE BASED HIS
 CALCULATIONS ON. I DID NOT FIND ONE WITH FASTENER
 SPACINGS OF 4"O.C. AT THE LAP AND THREE ROWS 8"O.C. IN
 THE FILED. FBC 107.2.1
  
 2) RAS 117 SECTION 8.1 STATES THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4"O.C.. THEREFORE,
 THE 3" O.C. IN THE ENGINEER'S CALCULATIONS CAN NOT BE
 USED. ADDITIONAL ROWS OF FASTENERS WILL BE REQUIRED.
 SUBMIT CORRECTED CALCULATIONS.
  
 3) CIRCLE OR HI-LIGHT THE SYSTEM, FASTENING OPTION AND
 DESIGN PRESSURE FOR THE PROPOSED ROOF COVERING ASSEMBLY
 ON THE PRODUCT APPROVAL. FBC 107