| Date |
Text |
| 2020-09-08 17:22:57 | |
| | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20070419 |
| | 9/8/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE |
| | MARKED AS PASSED OR FAILED. ADDITIONAL COMMENTS IN |
| | CAPITOL LETTERS WILL BE ADDED TO FAILED COMMENTS. |
| | |
| | 1) GAS ISOMETRIC: |
| | |
| | A) FAILED. PLEASE IDENTIFY THE REGULATOR AS EITHER NEW |
| | OR EXISTING. A SPEC SHEET FOR AN ITRON B42 REGULATOR |
| | HAS BEEN SUBMITTED, HOWEVER WHICH MODEL AND WHERE IT |
| | WILL BE INSTALLED NEEDS TO BE SHOWN ON THE DRAWING- |
| | SECTIONS G2421.1 & G2421.2 FBC RES. THE ITRON B42 HAS |
| | MANY DIFFERENT MODELS AND SIZES. PLEASE INDICATE THE |
| | MODEL NUMBER ON THE DRAWING AND SUBMIT SPECS FOR THAT |
| | MODEL INDICATING GAS PRESSURE RANGES AND ORIFICE SIZE. |
| | PLEASE COMPLY. |
| | |
| | B) FAILED. SHOW THE TOTAL LENGTH OF THE INTERIOR PIPING |
| | RUN FROM THE METER TO THE MOST REMOTE OUTLET. INDICATE |
| | THE BTUH LOAD OF EACH APPLIANCE TO CLARIFY HOW THE |
| | TOTAL 180,000 BTUH LOAD WAS DETERMINED- SECTIONS |
| | G2413.2, G2413.3, G2413.4.1, G2413.4.2. BECAUSE THE |
| | MAIN GAS PIPE FROM THE METER IS SUPPLYING THE NEW BBQ |
| | AND THE EXISTING SYSTEM A COMPLETE GAS PIPING REVIEW IS |
| | REQUIRED IN ORDER TO ENSURE A SAFE OPERATING SYSTEM FOR |
| | THE RESIDENCE- SEE SECTION G2412.4 FBC RES. PLEASE NOTE |
| | I WAS NOT ABLE TO LOCATE A PERMIT FOR THE EXISTING GAS |
| | APPLIANCES. IN ORDER TO ISSUE THE PERMIT FOR THE BBQ, |
| | ANY UNPERMITTED GAS PIPING AND APPLIANCE INSTALLATIONS |
| | MUST BE LEGALLY PERMITTED AND INSPECTED- SECTION 105 |
| | WPB. PROVIDE A COMPLETE ISOMETRIC DRAWING THAT INCLUDES |
| | BRANCH LINES TO ALL THE APPLIANCES AND EQUIPMENT IN THE |
| | RESIDENCE. PLEASE IDENTIFY THE APPLIANCES AND LIST THE |
| | BTUH CAPACITIES OF EACH. PLEASE NOTE THAT COMBUSTION |
| | AIR AND VENTING SYSTEMS SHALL BE REVIEWED AS PART OF |
| | THE APPROVAL PROCESS. |
| | |
| | C) FAILED. PROVIDE THE CORRECT PIPE SIZING TABLE- SEE |
| | SECTION G2413.4. PLEASE NOTE THAT LOW PRESSURE PIPING |
| | SYSTEMS FOR RESIDENTIAL APPLIANCE INSTALLATIONS ARE |
| | TYPICALLY SIZED USING TABLE G2413.4(1) FBC RES OR |
| | 402.4(2) FBC FG. PLEASE LIST THE CORRECT PIPE SIZING |
| | TABLE ON THE DRAWING. |
| | |
| | 2) FAILED. SUBMIT COMPLETE SPECS FOR THE BBQ SHOWING |
| | BTUH LOAD, GAS INPUT PRESSURE, AND INSTALLATION |
| | GUIDELINES INDICATING REQUIRED CLEARANCES TO |
| | COMBUSTIBLES, AND ANCHORING DETAILS- SECTION G2447.1. |
| | |
| | 3) PASSED. THE CONTRACTOR OR QUALIFIER WHO PREPARED THE |
| | DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION |
| | 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) & |
| | 471.025. |
| | |
| | 4) FAILED. THE $1500.00 PROJECT COST ON THE APPLICATION |
| | DOES NOT APPEAR TO INCLUDE THE BBQ GAS GRILL. PLEASE |
| | ADJUST THE VALUE TO INCLUDE THE COST OF THE GRILL- |
| | SECTION 109.3 WPB. THE PROJECT VALUE MAY INCREASE BASED |
| | ON COMMENT 1B LISTED ABOVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |