| 2020-07-22 16:26:57 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20070419 |
| | 7/22/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC: |
| | A) PLEASE IDENTIFY THE REGULATOR AS EITHER NEW OR |
| | EXISTING. A SPEC SHEET FOR AN ITRON B42 REGULATOR HAS |
| | BEEN SUBMITTED, HOWEVER WHICH MODEL AND WHERE IT WILL |
| | BE INSTALLED NEEDS TO BE SHOWN ON THE DRAWING- SECTIONS |
| | G2421.1 & G2421.2 FBC RES. THE ITRON B42 HAS MANY |
| | DIFFERENT MODELS AND SIZES. PLEASE INDICATE THE MODEL |
| | NUMBER ON THE DRAWING AND SUBMIT SPECS FOR THAT MODEL |
| | INDICATING GAS PRESSURE RANGES AND ORIFICE SIZE. |
| | B) SHOW THE TOTAL LENGTH OF THE INTERIOR PIPING RUN |
| | FROM THE METER TO THE MOST REMOTE OUTLET. INDICATE THE |
| | BTUH LOAD OF EACH APPLIANCE TO CLARIFY HOW THE TOTAL |
| | 180,000 BTUH LOAD WAS DETERMINED- SECTIONS G2413.2, |
| | G2413.3, G2413.4.1, G2413.4.2. |
| | C) PROVIDE THE CORRECT PIPE SIZING TABLE- SEE SECTION |
| | G2413.4. PLEASE NOTE THAT LOW PRESSURE PIPING SYSTEMS |
| | FOR RESIDENTIAL APPLIANCE INSTALLATIONS ARE TYPICALLY |
| | SIZED USING TABLE G2413.4(1) FBC RES OR 402.4(2) FBC |
| | FG. |
| | |
| | 2) SUBMIT COMPLETE SPECS FOR THE BBQ SHOWING BTUH LOAD, |
| | GAS INPUT PRESSURE, AND INSTALLATION GUIDELINES |
| | INDICATING REQUIRED CLEARANCES TO COMBUSTIBLES, AND |
| | ANCHORING DETAILS- SECTION G2447.1. |
| | |
| | 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | 4) THE $1500.00 PROJECT COST ON THE APPLICATION DOES |
| | NOT APPEAR TO INCLUDE THE BBQ GAS GRILL. PLEASE ADJSUT |
| | THE VALUE TO INCLUDE THE COST OF THE GRILL- SECTION |
| | 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |