| Plan Review Notes For Permit 20070414 |
| Permit Number |
20070414 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-21 14:43:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SHOW WHERE BRANCH CIRCUITS COME FROM | | | (PANEL(S)). SHOW PANEL LOCATION. | | | | | | SHOW POSSIBLE SIZE OF CONDUCTORS FROM EACH TRANSFORMER | | | LOCATION. | | | | | | PLANS ARE NOT SIGNED BY CONTRACTOR, PLEASE REMOVE | | | RIGHTHAND SIDE OF PLANS WITH ARCHITECTS NAME OR HAVE | | | THEM SIGN PLANS. |
|