2020-08-21 14:43:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW WHERE BRANCH CIRCUITS COME FROM
 (PANEL(S)). SHOW PANEL LOCATION.
  
 SHOW POSSIBLE SIZE OF CONDUCTORS FROM EACH TRANSFORMER
 LOCATION.
  
 PLANS ARE NOT SIGNED BY CONTRACTOR, PLEASE REMOVE
 RIGHTHAND SIDE OF PLANS WITH ARCHITECTS NAME OR HAVE
 THEM SIGN PLANS.