 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 GENERATOR PAD - PROVIDE DETAIL OF CAST-IN-PLACE
 CONCRETE SLAB WITH FASTNER SCHEDULE.
 DESIGNER/CONTRACTOR TO PRINT NAME AND SIGN PLAN.
  
 IF PRE-CAST SLAB IS USED
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
 3) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
  
 4) PROVIDE A SURVEY/SITE PLAN. SHOW LOCATION OF
 GENERATOR. PROVIDE SETBACKS TO STRUCTURE BUILDING
 OPENINGS AND PROPERTY LINES..
  