| Plan Review Notes For Permit 20070380 |
| Permit Number |
20070380 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-12-01 11:05:02 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF | | | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN | | | HEADING ?ANCHOR SPACING? PROVIDE INFORMATION FROM SHEET | | | 7 FL11973-R3. CORRECT ITEM #3; 12? EXCEEDS MAXIMUM | | | ANCHOR SPACING ALLOWED FOR POURED CONCRETE, MAXIMUM | | | SPAN 12?-0?, MAX LOAD (PSF) 62; C4 CONNECTION TYPE, ?? | | | TAPCON. | | | |
|