 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1 FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?WALL PRESSURE?; PROVIDE THE ACTUAL [PSF] FROM
 THE SUBMITTED DESIGN PRESSURE CALCULATIONS. CORRECT FOR
 ITEM # 1-8. PLEASE CORRECT COLUMN HEADING ?ANCHOR
 SPACING?; PROVIDE INFORMATION FROM PAGE 9 OF
 FL11973-R3. EXAMPLE: MAX LOAD (PSF) 62, SPANS UP TO
 12?; POURED CONCRETE; 2.5? EDGE DISTANCE; C2 CONNECTION
 TYPE TOP; ANCHOR TYPE ?? BCO ULTRACON MAXIMUM ANCHOR
 SPACING IS 9?. PLEASE VERIFY ALL ANCHOR SPACINGS USING
 CORRECT DESIGN PRESSURES, EDGE DISTANCE AND SPECIFIC
 ANCHOR TYPE USED.
 2. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION
  