| 2020-07-28 14:36:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20070360 313 N LAKESIDE CT |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | 1. AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING |
| | PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR |
| | THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| | NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| | LICENSED IN THAT TRADE. |
| | 2. PER WPB FBC 107.1, ALL PLANS TO BE SIGNED AND SEALED |
| | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. AS |
| | DESIGNER DOES NOT PROVIDE DIGITAL SIGNATURE IN |
| | ACCORDANCE WITH FAC AND FS, THEN THE DESIGNER SHALL |
| | PROVIDE PROPERLY SIGNED/SEALED PAPER DOCUMENT IN |
| | ACCORDANCE WITH FAC AND FS PRIOR TO PERMIT ISSUANCE. |
| | CALL 561-805-6724 FOR ADDITIONAL INFORMATION. |
| | 3. PER FBC FC 409.2, EVERY METER SHALL BE EQUIPPED WITH |
| | A SHUTOFF VALVE LOCATED ON THE SUPPLY SIDE OF THE |
| | METER. |
| | 4. PER WPB FBC 107.2.1, PROVIDE DOCUMENTATION THAT |
| | REGULATOR IS APPROVED FOR EXTERIOR APPLICATION. |
| | 5. SITE SURVEY SHOWING LOCATIONS OF GAS METER AND |
| | GENERATOR IS NOT LEGIBLE. PER WPB FBC 107.2.1, SUBMIT A |
| | LEGIBLE DRAWING/SURVEY, CLEARLY SHOWING THE SHOWING |
| | LOCATIONS OF GAS METER AND GENERATOR. |
| | 6. PER WPB FBC 107.2.1, SUBMIT THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | ALL PLANS TO BE SIGNED/ SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. PLEASE SEE COMMENTS #1 AND #2 |
| | ABOVE. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |