| 2020-07-20 12:45:41 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT-20070269 |
| | 7/20/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS ISOMETRIC IS INCOMPLETE: |
| | A) PROVIDE THE BTUH LOAD OF THE BBQ GRILL- SECTIONS |
| | G2413.2 & G2413.3 FBC RES. |
| | B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM- |
| | G2413.4.1 & G2413.4.2. |
| | C) PROVIDE THE PIPE SIZING TABLE USED- G2413.4 |
| | |
| | 2) SITE PLAN: PROVIDE THE UG TANK CLEARANCE DISTANCES |
| | MEASUREMENTS TO THE HOUSE, DRIVEWAY, AND PROPERTY LINE- |
| | SEE TABLE 6.4.1.1 AND SECTION 6.8.6.1 NFPA 58. PLEASE |
| | NOTE THAT IF THE TANK IS LESS TANK 10 FT. FROM THE |
| | DRIVEWAY, THE SHELL FOR THE TANK SHALL BE 18 IN. ABOVE |
| | GRADE, AND VEHICULAR BARRIER PROTECTION WILL BE |
| | REQUIRED. |
| | |
| | 3) THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS |
| | SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL ON THE |
| | DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE |
| | CODE SEC. 61G15-23.005. |
| | |
| | 4) PROVIDE SPECS FOR THE 2ND STAGE REGULATORS- G2421.1. |
| | |
| | 5) PLEASE NOTE THAT SPECS INDICATING GAS PIPING |
| | REQUIREMENTS FOR THE GENERATOR, POOL HEATER, AND BBQ |
| | GRILL SHALL EITHER BE SUBMITTED NOW OR BE ONSITE AT |
| | TIME OF INSPECTIONS. THE SPECS SHALL SHOW BTUH LOADS |
| | AND REQUIRED INPUT PRESSURES IN WATER COLUMN. |
| | |
| | 6) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS |
| | RISER DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- |
| | SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| | & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |