Plan Review Notes
Plan Review Notes For Permit 20070239
Permit Number 20070239
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-18 10:50:42SFR ELEVATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A FLOOR PLAN - SHOWING THE LOCATION
 AND DIMENSIONS OF THE ELEVATOR AND SURROUNDING AREA.
 2) DRAWINGS PROVIDED NEED TO BE SIGNED AND SEALED BY
 THE DESIGNER (ENGINEER).
 3) PLEASE PROVIDE DETAILS FOR THE ELEVATOR PIT.
 4) SHOW THAT TERMITE PROTECTION WILL BE REQUIRED ON THE
 DRAWINGS FOR THE DISTURBED EXISTING SOIL FBC R318
 5) SIGNED AND SEALED DRAWINGS AND DOCUMENTS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. DRAWINGS AND DOCUMENTS DO NOT SHOW IN
 "ADOBE READER" AS DIGITALLY/ELECTRONICALLY SIGNED. - OR
 - IF YOUR ENGINEER OR ARCHITECT DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY
 HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST
 FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT
 OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY E MAILING [email protected] AND ASKING FOR THE FORM.
  