| Date |
Text |
| 2020-08-11 11:04:15 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20070205 |
| | 8/11/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL |
| | EXISTS: |
| | 1) SHEET A020 AND OTHER ARCHITECTURAL PLANS SHOW ACCESS |
| | TO THE PUBLIC RESTROOM IS THROUGH THE STORAGE ROOM |
| | WHICH IS NOT PERMITTED PER SECTION 403.3.1 FBC P. |
| | THE ARCHITECT HAS REVISED SHEET A-020 TO SHOW A 438'-0" |
| | PATH OF TRAVEL FROM THE ENTRANCE TO THE NEW TENANT |
| | SPACE TO THE PUBLIC RESTROOM FACILITIES. IN THE |
| | NARRATIVE RESPONSE THE ARCHITECT IS CITING SECTION |
| | 403.3.3 FBC P WHICH APPEARS NOT TO BE RELEVANT BECAUSE |
| | THE SECTION REFERS TO "OCCUPANCIES" OTHER THAN MALLS. |
| | THE DEFINITION OF OCCUPANCY- THE PURPOSE FOR WHICH A |
| | BUILDING OR PORTION THEREOF IS UTILIZED OR OCCUPIED. |
| | THE CITY PLACE COMMON AREA DOES NOT APPEAR TO BE AN |
| | "OCCUPANCY". IF CITY PLACE IS IDENTIFIED AS AN "OPEN |
| | MALL" THEN THE ALLOWABLE TRAVEL DISTANCE IS 300 FT. PER |
| | SECTION 403.3.4 FBC P. |
| | PLEASE NOTE THAT THE DRAWING DOES NOT CLEARLY INDICATE |
| | THAT THE PATH TO THE RESTROOM FACILITIES IS AN |
| | ACCESSIBLE ROUTE- SEE SECTION 403.3.1. |
| | REFER TO SECTION 403.3 REQUIRED PUBLIC TOILET |
| | FACILITIES. |
| | CUSTOMERS, PATRONS AND VISITORS SHALL BE PROVIDED WITH |
| | PUBLIC TOILET FACILITIES IN STRUCTURES AND TENANT |
| | SPACES INTENDED FOR PUBLIC UTILIZATION. THE NUMBER OF |
| | PLUMBING FIXTURES LOCATED WITHIN THE REQUIRED TOILET |
| | FACILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 403 FOR ALL USERS. EMPLOYEES SHALL BE PROVIDED WITH |
| | TOILET FACILITIES IN ALL OCCUPANCIES. EMPLOYEE TOILET |
| | FACILITIES SHALL BE EITHER SEPARATE OR COMBINED |
| | EMPLOYEE AND PUBLIC TOILET FACILITIES. |
| | |
| | COMMENTS #5 AND #6 FROM THE 1AST REVIEW PRINTED BELOW |
| | ARE NOT COMPLETELY ADDRESSED. |
| | 5) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE |
| | DRINKING FOUNTAINS NOT SHOWN INCLUDING- |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| | 602.5. |
| | 6) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE |
| | BOTTLE FILLER NOT SHOWN INCLUDING- |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | C) REACH RANGES TO FILLER- SECTIONS 308 & 309. |
| | THE DETAILS PROVIDED FOR THE DRINKING FOUNTAIN AND |
| | BOTTLE FILLER ARE LABELED AS A KEY PLAN AND FITTING |
| | ROOM ELEVATION VIEWS. PLEASE LABEL THE DETAILS |
| | CORRECTLY. PLEASE NOTE THAT THE MEASUREMENTS SHOWN ON |
| | THESE DETAILS ARE THE MAXIMUM ALLOWABLE TO BE IN |
| | COMPLIANCE WITH THE ALLOWABLE REACH RANGE TO THE BOTTLE |
| | FILLER OVER THE DRINKING FOUNTAIN. |
| | |
| | COMMENT 7E BELOW STILL EXISTS. |
| | 7E) VENT CONTINUATION TO THE EXTERIOR OF THE BUILDING |
| | NOT SHOWN- SECTION 904.1. |
| | PLEASE CLARIFY THAT THE 2? VENT CONNECTION SHOWN IS THE |
| | CONNECTION TO THE MAIN VENT THAT IS TERMINATING TO THE |
| | OUTDOORS- SECTION 904.1 FBC P. |
| | |
| | NEW COMMENTS. |
| | 1) SHEET P-520: INCLUDE THE RPZ IN THE FIXTURE |
| | SCHEDULE. PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR WATER SERVICE BACKFLOW PREVENTERS- SECTION |
| | 107.2.1 WPB |
| | 2) P-520: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| | HEATER PER TABLE C404.2 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |