2020-08-10 14:51:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN INDICATION OF OPPOSING EXIT SIGNS AT THE
 REAR STOREROOM DOOR. THIS COMMENT IS RELATED TO # 3 OF
 THE PREVIOUS FIRE COMMENTS(ATTACHED BELOW FOR
 REFERENCE).
  
 THERE SHALL NOT BE OPPOSING EXIT SIGNS AT THIS
 LOCATION. EXIT SHALL BE IN ONE DIRECTION.
  
 ONE EXIT FROM THE STOREROOM IS PERMISSSIBLE AND IT IS
 LOCATED AT THE REAR EXTERIOR DOOR.
  
 THE EXIT PATH THROUGH THE STOREROOM SHALL BE 44" WIDE
 AND IDENTIFIED(MARKED) ON THE FLOOR(36.2.5.11)
  
 PLEASE CORRECT
  
  
 *****************3) SHEET A 020 - THERE IS AN
 INDICATION OF AN EXIT SIGN OVER THE REAR DOOR LEADING
 FROM THE SALES AREA TO AND THROUGH THE
 STOCKROOM.***************
  
 EXITING THROUGH THE STOCKROOM IS NOT ALLOWED PER FFPC,
 NFPA 101 CH 7 MEANS OF EGRESS.
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
  
 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE
 OCCUPANCIES THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C MERCANTILE
 OCCUPANCIES,
 SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED
 THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED
 THROUGH THE STOREROOM.
 (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
 (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN
 44 IN. (1120 MM) WIDE.
 (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT,
 AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
  
 ADDITIONALLY, ONE EXIT FROM THE SALES AREA MAY BE
 APPLICABLE PER NFPA 101, CH 38 (TYPO) 36
  
 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 36.2.5.3.
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY AS APPLICABLE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]