Plan Review Notes
Plan Review Notes For Permit 20070205
Permit Number 20070205
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-28 11:40:121ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20070205
 7/28/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A020 AND OTHER ARCHITECTURAL PLANS SHOW ACCESS
 TO THE PUBLIC RESTROOM IS THROUGH THE STORAGE ROOM
 WHICH IS NOT PERMITTED PER SECTION 403.3.1 FBC P.
  
 2) SHEET A030 ACCESSIBILITY: THE SINGLE OCCUPANCY
 TOILET DETAIL IS NOT IN COMPLIANCE FOR REQUIRED CLEAR
 FLOOR SPACES AND DOES NOT MATCH THE FLOOR PLANS.
 PROVIDE AN FBC ACC COMPLIANT, ENLARGED, SITE SPECIFIC,
 DIMENSIONED REST ROOM DRAWING INDICATING:
 A) CLEAR FLOOR SPACE DIMENSION FOR THE WATER CLOSET-
 SECTION 604.3
 B) CLEAR FLOOR SPACE DIMENSION FOR THE LAVATORY-
 SECTION 606.2
 C) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL -
 SECTION 604.2.
 D) TURNING CIRCLE DIAMETER- SECTION 304.3.
 E) DOOR OPENING DIMENSION AND DOOR SWING INTO THE ROOM-
 SECTION 603.2.3.
 F) GRAB LOCATIONS AND LENGTHS- SECTION 604.5
  
 3) SHEET A030: CORRECT THESE ELEVATION DRAWING DETAILS
 PER FBC ACC:
 A) GRAB BAR HEIGHTS FROM THE FINISHED FLOOR ARE SHOWN
 TO THE CENTERLINES OF THE GRAB BARS INSTEAD OF THE TOPS
 OF THE GRIPPING SURFACES- SECTION 609.4 FBC ACC.
 B) LAVATORY KNEE CLEARANCE DIMENSION TO THE UNDERSIDE
 OF THE FIXTURE NOT SHOWN- SECTION 306.3.3.
 WHERE KNEE CLEARANCE IS REQUIRED UNDER AN ELEMENT AS
 PART OF A CLEAR FLOOR SPACE, THE KNEE CLEARANCE SHALL
 BE 11 INCHES DEEP MINIMUM AT 9 INCHES ABOVE THE FINISH
 FLOOR OR GROUND, AND 8 INCHES DEEP MINIMUM AT 27 INCHES
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 STAFF SINK NOT SHOWN INCLUDING-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS- SECTIONS
 606.2, 305 & 306.
 B) MOUNTING HEIGHT OF THE SINK RIM OR COUNTER FROM THE
 FINISHED FLOOR- 606.3.
 C) REACH RANGE TO FAUCET AND COUNTER DEPTH- 606.4, 308
 & 309.
  
 5) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 DRINKING FOUNTAINS NOT SHOWN INCLUDING-
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 6) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 BOTTLE FILLER NOT SHOWN INCLUDING-
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 C) REACH RANGES TO FILLER- SECTIONS 308 & 309.
  
 7) P-510 RISERS:
 A) SHOW THE TRAP PRIMER CONNECTION- SECTION 1002.4.1
 FBC P
 B) PLEASE NOTE THAT TEMPERED WATER IS REQUIRED AT THE
 LAVATORY PER SECTION 416.5 SHOW THE LOCATION OF THE
 TEMPERATURE LIMITING DEVICE- SECTION 607.1.2.
 C) SHOW THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS TO THE FIXTURES- SEE SECTION 604.9.
 D) SHOW THE REQUIRED BACKFLOW PREVENTER AT THE REMOTE
 CHILLER- SECTION 608.3
 E) VENT CONTINIUATION TO THE EXTERIOR OF THE BUILDING
 NOT SHOWN- SECTION 904.1.
  
 8) 5-520: PLEASE ADD THE REQUIRED DEVICES LISTED ABOVE
 IN COMMENT 7 TO THE PLUMBING FIXTURE SCHEDULE- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  