Plan Review Notes
Plan Review Notes For Permit 20070205
Permit Number 20070205
Review Stop M
Sequence Number 1
Notes
Date Text
2020-07-22 08:57:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20070205
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS
 PROJECT. PLEASE INCLUDE THE DRESSING ROOM AREA IN THESE
 CALCULATIONS. FBC M 403
  
 2) PLEASE PROVIDE INFORMATION FOR THE AHU?S OR SHOW
 PROJECT NUMBER THAT THE INFORMATION IS LOCATED TO
 VERIFY INFORMATION ABOUT THE RTU?S. FBC FS 107.2.1
  
 3) PLEASE REMOVE THE ELECTRICAL LAYER FROM THE
 MECHANICAL SHEET FOR CLARITY. FBC FS 107.2.1
  
 4) PLEASE SHOW THE SMOKE DETECTORS ON THE DRAWINGS FOR
 EACH AHU. FBC M 606.2
  
 5) PLEASE EXPLAIN HOW THE DUCTWORK FOR THE DRESSING
 ROOMS EXHAUST ARE EXISTING. FBC FS 107.2.1
  
 6) PLEASE SHOW A MECHANICAL DEMO SHEET TO PLAINLY SHOW
 THE EXISTING MECHANICAL SYSTEMS. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  