Plan Review Notes
Plan Review Notes For Permit 20070205
Permit Number 20070205
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-07-08 11:21:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 020 - UNDER APPLICABLE CODES ON THE
 FIRE/LIFE SAFETY LINE THERE IS AN INDICATION OF THE
 BUILDING CODE.
  
 THERE IS NO INDICATION OF THE FLORIDA FIRE PREVENTION
 CODE ON THIS LINE OR ANY OTHER SECTION.
  
 THE PROPOSED PROJUECT SHALL COMPLY WITH THE 6TH ED OF
 THE FLORIDA FIRE PREVENTION CODE AND ALL ASSOCIATED
 NFPA CODES.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE.
  
  
  
  
 2) SHEET A 000 & A 020 - FIRE SPRINKLER AND FIRE ALARM
 WORK IS REQUIRED; HOWEVER, THERE ARE NO INDICATIONS
 THAT WORK WILL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWING.
  
 UNDER DEFERRED SUBMITTALS THERE ARE NO ENTRIES. FIRE
 SPRINKLER SHOP DRAWINGS AND FIRE ALARM SHOP DRAWINGS
 SHOULD BE UNDER THIS HEADING.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 3) SHEET A 020 - THERE IS AN INDICATION OF AN EXIT SIGN
 OVER THE REAR DOOR LEADING FROM THE SALES AREA TO AND
 THROUGH THE STOCKROOM.
  
 EXITING THROUGH THE STOCKROOM IS NO ALLOWED PER FFPC,
 NFPA 101 CH 7 MEANS OF EGRESS.
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
  
 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE
 OCCUPANCIES THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C MERCANTILE
 OCCUPANCIES,
 SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED
 THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED
 THROUGH THE STOREROOM.
 (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
 (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN
 44 IN. (1120 MM) WIDE.
 (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT,
 AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
  
 ADDITIONALLY, ONE EXIT FROM THE SALES AREA MAY BE
 APPLICABLE PER NFPA 101, CH 38
  
 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 36.2.5.3.
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY AS APPLICABLE.
  
  
  
 4) SHEET A 180 - THE DOOR SCHEDULE INDICATES "STANDARD
 THUMB TURNS (AT INTERIOR) FOR THE STOREFRONT DOOR # 55
  
 PER NFPA 101
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE
  
  
  
  
 5) SHEET A 180 - THE DOOR SCHEDULE INDICATES A
 STOREFRONT GRILLE , OVERHEAD ROLLING DOOR.
  
 THERE IS LIMITED DETAIL ON THE ROLLING DOOR
  
 PER NFPA 101
  
 36.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR
 DOORS
 COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE
 USED AS A PART
 OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE.
  
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES
 THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN
 THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY
 BY THE GENERAL PUBLIC.
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL
 BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN
 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT
 READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN
 WHEN THE SPACE IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED
 POSITION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE
 SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR
 EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED
 WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR
 DOOR
 ASSEMBLIES.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE
  
  
  
 6) SHEET A 180 - THE DOOR SCHEDULE INDICATES "EMERGENCY
 LOCK" DOOR # D2A, WITH NO DETAIL ON WHAT THIS IS OR
 WHAT IT MEANS IN FUNCTIONALITY.
  
 PER NFPA 101
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE
  
  
  
 7) SHEET A 110 - THERE IS NO INDICATION OF THE DOOR #
 OF THE REAR EGRESS DOOR THAT CAN BE CONFIRMED WITH ANY
 IN THE DOOR SCHEDULE.
  
 PLEASE REVIEW AND CORRECT AND ENSURE ALL EGRESS
 HARDWARE MEETS THE REQUIRMENTS AS NOTED ABOVE.
  
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]