Plan Review Notes
Plan Review Notes For Permit 20070205
Permit Number 20070205
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-14 13:38:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20070205
 ADD: 701 S. ROSEMARY AVE. # 141
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: KENT FAHEY
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 14TH/ 2020
 ACTION: DENIED
  
 1) THE DEMO SHEET NOTE # 4 INDICATES THE REMOVAL OF THE
 FRONT ENTRY DOORS AND FRAME IN ITS ENTIRETY. SHEET A420
 NOTE 26 INDICATES NEW EXTERIOR ALUMINUM NARROW STILE
 TEMPERED GLASS. I?M ASSUMING THIS WOULD BE THE DOORS,
 SIDELIGHTS, VERTICAL MULLIONS AND TRANSOM? THERE HAS
 BEEN NO WIND DESIGN CRITERIA OR PRODUCT APPROVALS
 SUBMITTED FOR THIS REVIEW.
  
 1A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 1A)(1). ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1A)(2). RISK CATEGORY.
  
 1A)(3). WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 1A)(4). APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1A)(5). DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1A)(6). TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 1B) PLEASE SHOW COMPLIANCE BY PROVIDING THE PRODUCT
 APPROVALS FOR ALL ELEMENTS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
 (B) WINDOWS, SIDELITES, TRANSOM & MULLIONS
  
 1C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
 1D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) SHEET A540 INDICATES THIS SHEET DETAILS THE CASH
 WRAP. PLEASE SHOW HOW THE CASH WRAP IS GOING TO COMPLY
 WITH:
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT. THE TOPS
 OF WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM
 AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND.
  
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 3A) SHEET A110 & A310 DETAIL # 7 THE ACCESSIBLE FITTING
 ROOM THERE APPEARS TO BE NO DOOR FOR ENTRY. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B ACCESS. CODE SECTION
 803.3 DOORS SHALL NOT SWING INTO THE DRESSING ROOM
 UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH
 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR.
  
 3B) PLEASE SHOW WITHIN THE ACCESSIBLE DRESSING ROOM
 COMPLIANCE WITH SECTIONS 803.4 BENCHES AND 803.5 COAT
 HOOKS.
  
 4) THE CODE SUMMARY & EGRESS SHEET A020 STATES AN
 OCCUPANT LOAD OF 55 OCCUPANTS. THEN STATES ONLY 1 IS
 ALLOWED/ REQUIRED. THAT 2 ARE ACTUALLY PROVIDES. THEN
 IT GOES ON TO STATING THE CODE SECTION 1016.2.5
 EXCEPTION 2 EGRESS THROUGH STORAGE ROOMS OF MERCANTILE
 OCCUPANCIES 2.1-2.4.
 THE FLOOR PLAN A100 DOES NOT SHOW HOW COMPLIANCE WITH
 FBC-B EXCEPTION 2- SECTIONS 2.1-2.4 ARE BEING COMPLIED
 WITH?
  
 5) SHEET A030 ACCESSIBILITY DETAILS:
 5A) THE WATER CLOSET GRAB BARS IS GIVEN WITH THE HEIGHT
 AT THE CENTERLINE OF THE GRAB BARS, NOT AT THE TOP OF
 THE BAR OR GRASPING SURFACE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 5B) THE WORDING ON THE PLAN IS CORRECT FOR MIRRORS BUR
 DEPICTED CORRECTLY. 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5C) THE DETAILS SHOW THE LOCATION OF THE TOILET PAPER
 DISPENSER BUT THE DISTANCE FORM IN FRONT OF THE WATER
 CLOSET.
 TOILET PAPER DISPENSERS. 604.7. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND THE GRAB BARS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  