| 2020-07-28 12:55:54 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20070190 |
| | 7/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC DRAWINGS: |
| | A) ON EACH RISER DRAWING, LIST THE GAS PIPE SIZING |
| | TABLES USED FOR THE SYSTEM- REFER TO SECTION G2413.4 |
| | AND TABLES- G2413.4(1) TO G2413.4(8) FBC RES. FUEL GAS. |
| | B) PROVIDE THE TOTAL BTUH LOAD OF EACH SYSTEM- SECTION |
| | G2413.2, G2413.4.1 & G2413.4.3. |
| | C) LABEL THE METERS AND REGULATORS AT METERS AS EITHER |
| | NEW OR EXISTING- G2412.3 AND SECTION 107.2.1 WPB. |
| | D) INDICATE THE BURIAL DEPTH OF THE PE AND PLACE A NOTE |
| | INDICATING A TRACER WIRE WILL BE INSTALLED- SECTIONS- |
| | G2415.12 AND G2415.17.3. SEE ALSO SECTION G2415.17.2 |
| | FOR APPROVED PE- METALLIC TRANSITION FITTINGS: SPECS |
| | FOR THE FITTINGS SHALL BE ONSITE FOR INSPECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |