Plan Review Notes
Plan Review Notes For Permit 20070178
Permit Number 20070178
Review Stop P
Sequence Number 5
Notes
Date Text
2021-01-25 12:52:0401/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-01:
 A. UNDER THE PLUMBING NOTE, FBC PLUMBING 2010 REFERS TO
 THE CHANGE TO THE CURRENT YEAR PER THE WPB AMENDMENTS
 TO THE FBC SEC. 101.4 REFERENCED CODES.
  
 B. PLEASE PROVIDE A NOTE THE HOT WATER LINE, NOT IN
 CONDITION SPACE, SHALL BE INSULATED WITH AN R-3 FACTOR
 PER THE 2017 F FBC RE 403.5.3.
  
 C. THERE APPEAR TO BE TWO ISOMETRIC DRAWINGS. THIS
 REVIEW WILL BE DONE ON P-01, SO PLEASE REMOVE THE P-01
 ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET P-02;
 A. THE CLEANOUT SHALL BE NO MORE THAN 10? FROM THE
 BUILDING ENTRANCE. PLEASE PROVIDE A DISTANCE ON THE
 FLAT DRAWING TO COMPLY WITH 201 FBC SEC. R P3005.2.3
 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 B. ON THE WASHING MACHINE STACK, PLEASE SHOW THE P-TRAP
 ABOVE GROUND AND A VENT ( A.A.V. OR VTR) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THE WATER CLOSET IN THE POWDER ROOM IS NOT VENTED.
 PLEASE VENT WITH LAV PER THE 2017 FBC SEC R 3101.2.1
 VENTING REQUIRED.
  
 D. THE KITCHEN IS SHOWN AS AN UNDER THE GROUND P-TRAP
 AND NOT VENTED CORRECTLY; PLEASE CHANGE TO ABOVE GROUND
 AND VENT TO COMPLY WITH THE 2017 FBC SEC R 3101.2.1
 VENTING REQUIRED.
  
 C. THE PATIO SIN IS ON A WENT VENT BATHROOM GROUP.
 PLEASE MOVE DOWNSTREAM PER THE 2017 FBC SECTION R3108.1
 HORIZONTAL WET VENT PERMITTED.
  
 3. PLEASE COMPLY WITH SIGNATURE REVIEW COMMENTS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET P-04, THE DRAIN LINE ON THE TANKLESS WATER
 HEATER MAY BE A CONDENSATE LINE AND, IF SO, WILL BE
 REQUIRED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017
 FBC SEC. R318.5.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  