| 2021-01-25 09:41:47 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT |
| | FROM UTILITY. |
| | |
| | AIC RATING OF SERVICE DISCONNECT AND PANEL |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| | |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| | FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| | NOT LESS THAN 10,000 AMPERES. (110.9) |
| | E3706.1PANELBOARD RATING. |
| | ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT |
| | OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR |
| | THE CALCULATED LOAD. (408.30) |
| | |
| | 2. PROVIDE EQUIPMENT SERVICE OUTLET PER E3901.12 |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | 3. OUTLETS REQUIRED AT ISLAND SINK PER FIGURE 3901.4.1 |
| | ISLAND COUNTERTOP SPACES. |
| | E3901.4.2 ISLAND COUNTERTOP SPACES. |
| | AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| | EACH ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF |
| | 24 INCHES (610 MM) OR GREATER AND A SHORT DIMENSION OF |
| | 12 INCHES (305 MM) OR GREATER. [210.52(C)(2)] |
| | |
| | 4. SMOKE ALARMS |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. 1.IN EACH SLEEPING ROOM. |
| | 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE |
| | IMMEDIATE VICINITY OF THE BEDROOMS. |
| | NOTE: ADD SMOKE ALARMS IN THE IMMEDIATE VICINITY OF THE |
| | BEDROOMS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |