| Plan Review Notes For Permit 20070178 |
| Permit Number |
20070178 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-15 21:53:46 | 1ST REVIEW FBC-2017 GAS | | | PERMIT-20070178 | | | 9/15/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER | | | AND THE RANGE THE 2017 FBC FUEL GAS SEC. 304.1, 614.5 | | | (CLOTHES DRYERS) 304.4MAKEUP AIR PROVISIONS, | | | 304.5INDOOR COMBUSTION AIR (RANGE) | | | | | | 2. SUBMIT MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1- 2ND | | | REQUEST. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | | | | | | 2020-09-15 18:47:13 | IN REVIEW |
|