| 2020-08-03 12:06:34 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20070178 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE ENERGY SUBMITTAL. FBC EC 101.5.1.1.2 |
| | |
| | 2) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS. |
| | FBC EC R403.7 & FBC RES M1401.3 |
| | |
| | 3) ALL DUCTWORK IN THE GARAGE FOR AHU-1 SHALL BE METAL |
| | AND 26 GAUGE. FBC RES R302.5.2 |
| | |
| | 4) THE PIPING FOR NOTE 10 ON SHEET M-1 MUST BE METAL 26 |
| | GAUGE AND MUST TERMINATE IN THE RETURN DUCTWORK, NOT |
| | TERMINATE UNDER THE AHU. FBC RES R302.5.2 |
| | |
| | 5) PLEASE SHOW DUCTWORK FOR RETURN AIR FOR AHU-1 AT |
| | GARAGE IS METAL 26GAUGE. FBC RES R302.5.2 |
| | |
| | 6) PLEASE PROVIDE INFORMATION FOR THE XVENT AT THE |
| | DRYER DUCT TERMINATION POINT MEETS SECTION; FBC RES |
| | M1502.3 ( THE TERMINATION POINT CAN NOT HAVE A SCREEN) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |