2020-07-16 08:53:27ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) -
 SEE NOTE NUMBER 9 OR GENERAL LIMITATION NUMBER 7 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND
 DESIGN DATA USED PER 2017 FBC AND ASCE 7-10 - WIND
 SPEED - EXPOSURE - RISK CATEGORY - ETC.
 2) YOU HAVE 2 PRODUCT APPROVALS FOR THE FLAT DECK -
 PLEASE REMOVE 1 OF THEM FROM THE FOLDERS (FL 2533-R21)
 AND (MIAMI DADE 20-0131.01) OR STATE ON THE PRODUCT
 APPROVAL WHAT EACH ONE IS FOR.