Plan Review Notes
Plan Review Notes For Permit 20070135
Permit Number 20070135
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-28 13:03:4707/28/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. A BACKFLOW (PVB) IS REQUIRED ON THE AUTOFILL PER THE
 2017 FBC-PLUMBING SEC.608.1 AND A REDUCE PRESSURE ZONE
 VACUUM BREAKER ASSEMBLY IS REQUIRED AT METER PER THE
 CITY OF WEST PALM BEACH CROSS CONNECTION PROGRAM.
  
 3. PLANS SHOW A POOL HEATER PLEASE CLARIFY IS IT GAS OR
 IS IT ELECTRIC, AS A GAS AND SPA HEATERS SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82 % AND AS A HEAT PUMP
 POOL HEATERS SHALL HAVE A MINIMUM COP OF 4.0 WHEN
 TESTED IN ACCORDANCE WITH AHRI 1160 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. IF THERE IS A POOL HEATER, PLEASE PROVIDE
 SPECIFICATIONS PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  