| 2020-08-11 10:50:27 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) CODE SECTION SHOWN ON THE STAIR SECTION DRAWINGS FOR |
| | THE STAIR HANDRAILS IS INCORRECT FBC R311.7.7 SHOULD BE |
| | FBC R311.7.8 |
| | 2) DOOR FROM GARAGE LABELED (120) CANNOT OPEN INTO THE |
| | BEDROOM PER FBC R302.5.1 |
| | 3) DOOR SCHEDULE SHOWS 2 TYPE (F) DOORS - PLEASE |
| | CLARIFY THE DOOR TYPE FROM GARAGE TO LIVING SPACE TO |
| | COMPLY WITH FBC R302.5.1 |
| | 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE INSTALLED |
| | - OR - PROVIDE A STATEMENT ON THE DRAWINGS AS TO THE |
| | REFERRAL OF THE ROOFING SYSTEM PER FBC WPB AMENDMENTS |
| | 107.3.4.1 DEFERRED SUBMITTAL. |
| | 5) THE PROVIDED STORM WATER CALCULATIONS NEED TO BE |
| | SIGNED AND DATED BY THE ENGINEER. |
| | 6) SHOW THE REQUIRED FLOOD VENTS IN THE GARAGES PER FBC |
| | R322.2.2 |
| | 7) DRAWINGS AND DOCUMENTS DO NOT SHOW IN "ADOBE READER" |
| | AS DIGITALLY/ELECTRONICALLY SIGNED. "ADOBE READER" |
| | STATES "AT LEAST ONE SIGNATURE HAS PROBLEMS". PLEASE |
| | CHECK TO SEE THAT THE ELECTRONIC SIGNATURES ARE CARRIED |
| | OVER PROPERLY. SIGNED AND SEALED DRAWINGS AND DOCUMENTS |
| | IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY |
| | SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. |
| | |
| | |