| Plan Review Notes For Permit 20070049 |
| Permit Number |
20070049 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-08-03 14:13:27 | WINDOWS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 4TH REVIEW - PLEASE READ THE CORRECTION COMMENTS | | | CAREFULLY | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) THE ENGINEERING SUPPLIED SHOWING THE WIND DESIGN | | | PRESSURES FROM "ENGINEERING EXPRESS" SHOWS THE REQUIRED | | | POSITIVE PRESSURES AT (+58.9) THE PRODUCT APPROVALS FOR | | | THE SNGLE HUNG AND THE FIXED GLASS SHOW A MAXIMUM | | | PRESSURE OF (+55) - PLEASE PROVIDE PRODUCT APPROVALS | | | THAT MEET OR EXCEED THE REQUIRED WIND DESIGN PRESSURES | | | SHOWN ON THE "ENGINEERING EXPRESS" DOCUMENT PROVIDED. | | | 2) THE SIGNED AND SEALED ENGINEERING FROM "ENGINEERING | | | EXPRESS" = | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG | | | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON | | | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] | | | AND ASKING FOR THE FORM. |
|