| 2020-07-24 11:29:10 | WINDOWS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) THE ENGINEERING SUPPLIED SHOWING THE WIND DESIGN |
| | PRESSURES FROM "ENGINEERING EXPRESS" SHOWS THE REQUIRED |
| | POSITIVE PRESSURES AT (+58.9) THE PRODUCT APPROVALS FOR |
| | THE SNGLE HUNG AND THE FIXED GLASS SHOW A MAXIMUM |
| | PRESSURE OF (+55) - PLEASE PROVIDE PRODUCT APPROVALS |
| | THAT MEET OR EXCEED THE REQUIRED WIND DESIGN PRESSURES. |
| | 2) THE SIGNED AND SEALED ENGINEERING FROM "ENGINEERING |
| | EXPRESS" = |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| | ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| | AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS |
| | MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN |
| | REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING |
| | DEPT.) |