| Date |
Text |
| 2020-09-09 13:45:23 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20070030 |
| | 9/9/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1ST REVIEW COMMENTS #5, 6, 8, 9, 10, 11 PRINTED BELOW |
| | HAVE NOT BEEN COMPLETED ADDRESSED. |
| | |
| | 5) P100 & P102: THE 3" STACK CANNOT SERVE AS THE WET |
| | VENT FOR THE POWDER ROOM WATER CLOSET AND LAVATORY- |
| | SECTION P3108.2 FBC RES. THE WATER CLOSET IS NOT |
| | VENTED. |
| | |
| | 6) P100 & P102: NO VENT IS SHOWN FOR THE ICE MAKER |
| | TRAP- SECTION P3101.2.1 & P3105.1. THE REVISED DRAWING |
| | DOES NOT SHOW A VENT FOR THE TRAP. |
| | |
| | 8) P101 & P102: THE RISER SHOWS AN INCORRECT 2" |
| | HORIZONTAL DRAIN EXTENDING FROM THE 3" LAUNDRY WASTE |
| | STACK TO THE MAIN DRAIN- A MINIMUM 3" DRAIN IS |
| | REQUIRED- SECTION P3005.1.6. A 3" STACK VENT FOR THE 3" |
| | WASTE STACK SHALL BE PROVIDED PER SECTION P3109.3 FBC |
| | RES. THE 2" DRY VENT EXTENDING FROM THE MUD ROOM SINK |
| | SHALL NOT CONNECT HORIZONTALLY INTO THE WASTE STACK AT |
| | A POINT BELOW THE 2ND FLOOR CLOTHES WASHER DRAIN |
| | CONNECTION- SECTIONS P3109.3 AND P3104.5. |
| | |
| | 9) P100 & P102: THE DRY VENT FOR THE WET VENT SERVING |
| | BATH 109 THAT IS EXTENDING FROM THE SHOWER DRAIN SHALL |
| | EXTEND TO THE OPEN AIR- SECTIONS P3108.2.1 & P3104.1. |
| | THE DRY VENT FROM BATH 109 LAV AND SHALL NOT CONNECT |
| | INTO THE 3" SOIL STACK BECAUSE OF POSSIBLE BLOCKAGE OF |
| | THE LAV VENT-SECTION P3104.5. THE REVISED PLAN SHOWS A |
| | 2" VTR FOR THE FIXTURES WHICH IS CODE COMPLIANT. |
| | |
| | 10) PROVIDE A WATER RISER DRAWING- SECTION 107.3.5.3 |
| | WPB. PLEASE INCLUDE IN THE RISER THE LOCATIONS OF |
| | SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND BACKFLOW |
| | PREVENTERS WHERE REQUIRED- SECTIONS P2902.3 & P2903.5. |
| | REFER TO SECTION R403.5.1 FBC EC: CIRCULATION PUMPS FOR |
| | HEATED WATER CIRCULATION SYSTEMS ARE NOT OPTIONAL. |
| | PLEASE CORRECT NOTE #5 ON SHEET P106 AND VERIFY THE NEW |
| | AO SMITH WATER HEATERS WILL BE EQUIPPED WITH INTEGRAL |
| | CIRCULATION PUMPS. |
| | |
| | 11) PROVIDE EQUIPMENT SCHEDULES FOR THE WATER HEATERS |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS SECTIONS |
| | P2801.3 & G2448.1. PLEASE SHOW THE LOCATIONS OF THE |
| | WATER HEATERS ON THE PLUMBING FLOOR PLAN DRAWINGS. |
| | PLEASE NOTE THAT THE GAS PIPING INSTALLATIONS SHALL BE |
| | UNDER SEPARATE PERMIT- SECTIONS 105.3 & 107.1 WPB (SEE |
| | GAS COMMENTS FOR FURTHER INFORMATION). PLEASE NOTE THAT |
| | COMPLIANCE DATA FOR THE WATER HEATERS SHALL BE LISTED |
| | IN THE REQUIRED ENERGY COMPLIANCE REPORT- SEE TABLE |
| | C404.2 FBC EC. MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATERS WERE NOT SUBMITTED. PLEASE SUBMIT SPECS |
| | INCLUDING TEMPERATURE RISE AND GPM FLOW SIZING CHARTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |