| 2020-08-03 15:48:19 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20070030 |
| | 8/3/2020\ |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P100, P101, & P102 CABANA BATH AND BATH #4: |
| | THE DISTANCES FROM THE SHOWER DRAIN TRAPS TO THE COMMON |
| | VENT APPEAR TO EXCEED THE MAXIMUM 6" ALLOWABLE DISTANCE |
| | PER TABLE P3105.1 FBC RES. |
| | |
| | 2) P100 & P102: THE COMMON VENT FOR THE SINKS AT THE |
| | WET BAR AND BUTLER'S PANTRY SHALL EXTEND TO THE OPEN |
| | AIR- SECTION P3104.1. |
| | |
| | 3) P100 & P102: PROVIDE A VTR SYMBOL FOR THE AT THE |
| | CONNECTION OF THE TWO VENT STACKS RISING FROM BATH #3 & |
| | 4- SECTIONS P3102.1 & P3104.1. |
| | |
| | 4) P101 & P102: VERIFY THE SHOWER DRAIN IN BATH #3 WILL |
| | CONNECT TO THE VERTICAL VENT ABOVE OR AT THE SAME |
| | ELEVATION AS THE TWO WATER CLOSETS- SECTION P3108.4. |
| | |
| | 5) P100 & P102: THE 3" STACK CANNOT SERVE AS THE WET |
| | VENT FOR THE POWDER ROOM WATER CLOSET AND LAVATORY- |
| | SECTION P3108.2. |
| | |
| | 6) P100 & P102: NO VENT IS SHOW FOR THE ICE MAKER TRAP- |
| | SECTION P3101.2.1 & P3105.1. |
| | |
| | 7) P101 & P102 MASTER BATH: THE DISTANCE FROM THE |
| | SHOWER DRAIN TRAP TO THE COMMON VENT APPEARS TO EXCEED |
| | THE MAXIMUM 6" ALLOWABLE DISTANCE PER TABLE P3105.1 FBC |
| | RES. IF THE INTENTION IS THE WET VENT THE SHOWER PLEASE |
| | NOTE THAT NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN |
| | SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE |
| | DRAIN CONNECTION. THE DRAWING SHOWS TWO. |
| | |
| | 8) P101 & P102: THE RISER SHOWS AN INCORRECT 2" |
| | HORIZONTAL DRAIN EXTENDING FROM THE 3" LAUNDRY WASTE |
| | STACK TO THE MAIN DRAIN- A MINIMUM 3" DRAIN IS |
| | REQUIRED- SECTION P3005.1.6. |
| | |
| | 9) P100 & P102: THE DRY VENT FOR THE WET VENT SERVING |
| | BATH 109 THAT IS EXTENDING FROM THE SHOWER DRAIN SHALL |
| | EXTEND TO THE OPEN AIR- SECTIONS P3108.2.1 & P3104.1. |
| | |
| | 10) PROVIDE A WATER RISER DRAWING- SECTION 107.3.5.3 |
| | WPB. PLEASE INCLUDE IN THE RISER THE LOCATIONS OF |
| | SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND BACKFLOW |
| | PREVENTERS WHERE REQUIRED- SECTIONS P2902.3 & P2903.5. |
| | |
| | 11) PROVIDE EQUIPMENT SCHEDULES FOR THE WATER HEATERS |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS SECTIONS |
| | P2801.3 & G2448.1. PLEASE SHOW THE LOCATIONS OF THE |
| | WATER HEATERS ON THE PLUMBING FLOOR PLAN DRAWINGS. |
| | PLEASE NOTE THAT THE GAS PIPING INSTALLATIONS SHALL BE |
| | UNDER SEPARATE PERMIT- SECTIONS 105.3 & 107.1 WPB (SEE |
| | GAS COMMENTS FOR FURTHER INFORMATION) .PLEASE NOTE THAT |
| | COMPLIANCE DATA FOR THE WATER HEATERS SHALL BE LISTED |
| | IN THE REQUIRED ENERGY COMPLIANCE REPORT- SEE TABLE |
| | C404.2 FBC EC. |
| | |
| | 12) A100 & A102: PROVIDE COMPLETE DIMENSIONS FOR THE |
| | SHOWERS ON THE PLAN AND PROVIDE SHOWER PAN DETAILS PER |
| | SECTIONS P2708.1 & P2709.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |